Waste heat from baking ovens keeps buffer tank temperature stable
The cleaning cycle at this industrial bakery was being disrupted by an undersized buffer tank. A larger stratified buffer tank, combined with waste heat from the baking ovens, now provides the stability the process needs. Hot water is always available without driving up energy consumption.
Project overview: technical specifications
Customer
Industrial bakery
Problem
Undersized hot water buffer tank for the cleaning process
Solution
Stratified buffer tank with waste heat recovery via two condensers
Buffer volume
80 m³
Required temperature
65 °C
Energy sources
Waste heat from production + gas-fired boiler (backup)
Limited buffer capacity and a poor layout held back the cleaning cycle
The first challenge? Not enough high-pressure hot water. On top of that, the hot water had to be available at all times so the machines could be cleaned on schedule.
The small buffer tank soon turned out to be the culprit. It lacked the capacity to absorb peak demand and was regularly drained. Refilling it with hot water every time took far more energy than necessary.
The second challenge was the layout. The buffer system stood in the middle of the production hall, where it got in the way of daily operations. So we moved the entire system to an outdoor unit.
Large-scale buffering and waste heat recovery ensure a continuous hot water supply
Stratified buffer tank makes the most of available energy
Callens engineered and installed an 80 m³ stratified buffer tank. Cold water, at approximately 15 °C, enters at the bottom. The condensers heat the water to 65 °C, after which it is fed back into the top of the buffer tank.
With this design it is possible to store energy efficiently and make it available at the right time, even when demand varies significantly.
Waste heat from condensers supplies the buffer tank
Two condensers on the production lines recover heat from the airflows. This heat is used to warm the water, which is then injected into the top of the buffer tank.
Capacity per condenser
43 kW
Exhaust air inlet temperature
175 °C
Exhaust air outlet temperature
69 °C
Exhaust airflow (full load)
1,200 m3/h
A major advantage: the condensers can run continuously, regardless of the immediate heat demand. That way, the system recovers as much energy as possible, even when production fluctuates.
For peak demand or exceptional circumstances, we switch on a gas-fired boiler connected to a heat exchanger. In practice, it’s hardly ever needed, because heat recovery covers most of the energy demand.
Project Engineer
-
Callens
Compact outdoor container unit
To free up space in the production hall, we moved the entire system into an outdoor container, which we built from scratch. It houses all the technical components:
pumps for water supply and circulation
treatment units for the cleaning water
hydraulic connections to the buffer tank
central heating boiler with heat exchanger
Technical refinements make the difference
Maintaining stratification in the buffer tank was a challenge in its own right. That’s why we fitted the tank with four suction lances to draw off water. If the water level drops, there’s always another suction lance that can reach the hot top layer.
In just one month, the waste heat recovery system heated 240 m³ of water without using the gas-fired boiler. This demonstrates the system’s potential to reduce fossil fuel use.
Project Engineer
-
Callens
When is this type of solution a good fit?
This solution is particularly suitable for production environments where:
large volumes of hot water are required for cleaning or process applications
waste heat is available from ovens, airflows, or other systems
heat demand fluctuates significantly over time
optimizing space in the production environment is important